REAL Alternatives Module 2 Design Differences for Alternative Refrigerants | 17 2.6 Two stage compression (booster) Excessively high discharge temperature will occur on low temperature (frozen food) systems that reject their heat to ambient air. To avoid this, two stages of compression are used. The interstage between the low and high stage compressors is generally cooled by the suction gas from the high temperature load and the gas from the receiver pressure regulating valve. The diagram in below is a typical transcritical booster system commonly used in retail applications. EEV EEV C1 C2 The gas from the low temperature evaporator enters the suction of the low stage compressor (C1). This compressor discharges into the suction of the high stage compressor (C2). The gas from the high temperature load, and the gas from the receiver pressure regulating valve also enters the suction of the high stage compressor (C2). transcritical booster system Gas cooler regulation valve Receiver pressure regulation valve

PDF Image | Alternative Refrigerants

alternative-refrigerants-017

PDF Search Title:

Alternative Refrigerants

Original File Name Searched:

RealAlternatives-2-Design-differences-Feb15.pdf

DIY PDF Search: Google It | Yahoo | Bing

CO2 Organic Rankine Cycle Experimenter Platform The supercritical CO2 phase change system is both a heat pump and organic rankine cycle which can be used for those purposes and as a supercritical extractor for advanced subcritical and supercritical extraction technology. Uses include producing nanoparticles, precious metal CO2 extraction, lithium battery recycling, and other applications... More Info

Heat Pumps CO2 ORC Heat Pump System Platform More Info

CONTACT TEL: 608-238-6001 Email: greg@infinityturbine.com | RSS | AMP