Text from PDF Page: 041
HPWH Performance Report Installation Notes: • Took out 284-litre (75 gal) electric water heater • Put in 315-litre (80-gallon) water tank • About 1.7 meters (5.5 feet) of pipe length from wall to outdoor unit • No heat trace temperature control • Redundant pressure reducing valves, 50 psig then 90 psig Updates/Issues: • 12/5/16 23:16 – Outdoor unit cut out and threw error code e111 with "Replace PCB Board" as corrective action • 12/14/2016 – PCB board replaced, outdoor unit froze up due to GFCI outlet to heat trace not being on and OAT between 10-20F, outdoor unit sitting in error code 073 • 12/16/2016 – Outdoor unit thawed out, leak detected at pump • 12/17/16 – Outdoor unit replaced, gave error codes 073, 111, and 111 within the first hour • 12/18/2016 2:13 – System back up to temperature • 2/18/2017 – Water collecting inside of outdoor unit by PCB, Outdoor unit infiltration hole to control board blocked with tape to prevent further moisture issues. 30PDF Image | CO2 Integrated Heat Pump Water Heater
PDF Search Title:
CO2 Integrated Heat Pump Water HeaterOriginal File Name Searched:
CO2-Integrated-Heat-Pump-perf.pdfDIY PDF Search: Google It | Yahoo | Bing
CO2 Organic Rankine Cycle Experimenter Platform The supercritical CO2 phase change system is both a heat pump and organic rankine cycle which can be used for those purposes and as a supercritical extractor for advanced subcritical and supercritical extraction technology. Uses include producing nanoparticles, precious metal CO2 extraction, lithium battery recycling, and other applications... More Info