logo

CO2 Product Guide 2021

PDF Publication Title:

CO2 Product Guide 2021 ( co2-product-guide-2021 )

Previous Page View | Next Page View | Return to Search List

Text from PDF Page: 026

Capacity data Application expansion valve and liquid injection valve Valve type Condensing temperature (°C) Subcooling Nominal capacity kW (R744) EX4 -10°C 1K 3...33.5 EX5 10...102 EX6 24...244 EX7 70...670 EX8 180...1789 26 Guideline for selection of electrical control valves as expansion valves Controls navigator For easy and quick selection of Electrical Control Valves as Expansion Valves, the “Controls Navigator” selection tool can be downloaded from the website at climate.emerson.com/en-gb. The following guideline should be taken into consideration in order to obtain full advantages of the control valves: • Published capacities are maximum and there are no reserve capacities • Shorter travel time i.e. faster response also for larger size of valve. For example, the EX7 has a maximum travel time of 3.2 seconds. The valve has approximately 1.6 seconds travel time at 50% capacity operation.

PDF Image | CO2 Product Guide 2021

co2-product-guide-2021-026

PDF Search Title:

CO2 Product Guide 2021

Original File Name Searched:

2021-co2-refrigeration-4217772.pdf

DIY PDF Search: Google It | Yahoo | Bing

CO2 Organic Rankine Cycle Experimenter Platform The supercritical CO2 phase change system is both a heat pump and organic rankine cycle which can be used for those purposes and as a supercritical extractor for advanced subcritical and supercritical extraction technology. Uses include producing nanoparticles, precious metal CO2 extraction, lithium battery recycling, and other applications... More Info

Heat Pumps CO2 ORC Heat Pump System Platform More Info

CONTACT TEL: 608-238-6001 Email: greg@infinityturbine.com | RSS | AMP