Comparison of R744 and R410A

PDF Publication Title:

Comparison of R744 and R410A ( comparison-r744-and-r410a )

Previous Page View | Next Page View | Return to Search List

Text from PDF Page: 053

this increased capacity would have the practical benefit of reduced dependence on lower-efficiency supplementary heating. The size of the heat exchangers for R744 and R410A are basically the same for R410A and R744 in systems designed for comfort. In heating, at a supply air temperature of 40oC, R744 and R410 have approximately the same efficiency for a given indoor coil size. Above a supply air temperature of 40oC, R744 has higher efficiency for a given size heat exchanger (or equivalently, a smaller heat exchanger would have the same efficiency). In cooling, the comfort condition determines the evaporating temperature and the indoor coil size is predominately a function of the airflow rate. In heating if the fan power required to move air over the outdoor coil in the system COP calculation, the optimum airflow over the outdoor coil is around 0.15 kg/s per kW heating capacity for both R410A and R744. In cooling, in terms of system COP there is an optimum for R410A, but not for R744. 42

PDF Image | Comparison of R744 and R410A

PDF Search Title:

Comparison of R744 and R410A

Original File Name Searched:

CR039.pdf

DIY PDF Search: Google It | Yahoo | Bing

CO2 Organic Rankine Cycle Experimenter Platform The supercritical CO2 phase change system is both a heat pump and organic rankine cycle which can be used for those purposes and as a supercritical extractor for advanced subcritical and supercritical extraction technology. Uses include producing nanoparticles, precious metal CO2 extraction, lithium battery recycling, and other applications... More Info

Heat Pumps CO2 ORC Heat Pump System Platform More Info

CONTACT TEL: 608-238-6001 Email: greg@infinityturbine.com (Standard Web Page)