Text from PDF Page: 039

7.3.3 Installing an outdoor unit on a timber deck Figure 7.16 Fixing unit to a timber deck • Fix hot-dip galvanised mounting rails into the joists with 75 mm long stainless steel screws. Alternatively, fix the mounting rails to 140 x 45 H3.2 treated timber rails laid on flat that are screw- fixed to the decking joists with 115 mm long stainless steel screws (Figure 7.16). Provide anti-vibration mounts or pads. Fix hot-dip galvanised mounting rails through the rails and joists with 75 mm long stainless steel screws. • Check that rails are level before tightening – pack with plastic shims as necessary to level (Figure 7.17). • Fix the unit to the rails and tighten fixing bolts. anti-vibration mounts 190 × 45 H3.2 treated timber rails screw- fixed to joists fix at centres to suit unit timber decking joists Figure 7.17 Pack with plastic shims to level 7.3.4 Installing an outdoor unit on a foundation or wall (concrete/concrete masonry only) Figure 7.18 Wall-mounted unit on brackets – masonry wall • Check the structural integrity of the wall or foundation. • Bolt fix hot-dip, galvanised brackets or proprietary brackets to the wall or foundation using stainless steel masonry anchors or screw bolts (Figure 7.18). • Check that the brackets are level before tightening. • Waterproof around fixings according to the material. • Fix the unit to the brackets. • Anti-vibration pads may be used. • Ensure the ground underneath is stable, compact and level. bracket spacing to suit unit footings galvanised mild steel brackets bolt-fixed to wall with stainless steel masonry anchors maintain minimum distance between unit and wall (manufacturer’s recommendation or 150 mm min.) Note: Outdoor units may be able to be wall-mounted to some lightweight claddings but the connections and weatherproofing details must be specifically designed to maintain the integrity of the weatherproofing. 39

PDF Image | Heat pump installation Good Practice Guide

heat-pump-installation-good-practice-guide-039

PDF Search Title:

Heat pump installation Good Practice Guide

Original File Name Searched:

Good_practice_heat_pump_installation.pdf

DIY PDF Search: Google It | Yahoo | Bing

CO2 Organic Rankine Cycle Experimenter Platform The supercritical CO2 phase change system is both a heat pump and organic rankine cycle which can be used for those purposes and as a supercritical extractor for advanced subcritical and supercritical extraction technology. Uses include producing nanoparticles, precious metal CO2 extraction, lithium battery recycling, and other applications... More Info

Heat Pumps CO2 ORC Heat Pump System Platform More Info

CONTACT TEL: 608-238-6001 Email: greg@infinityturbine.com | RSS | AMP