PDF Publication Title:
Text from PDF Page: 029
Fig. 5.23. A schema of the vertical ground heat pump (Source: Smuczyńska, 2015) Fig. 5.24. Drilling of boreholes (Source: Smuczyńska, 2015) In case of horizontal closed loops (Fig. 5.25) a sufficient land area is needed. The PVC, PB and PE pipes are used most frequently. The distance between pipes depends on the technology used and mostly is in a range between 0.8 and 1.0 m (Fig. 5.26). The advantages of this system are: low cost of work connected with shallow depth of pipes (about 1.5 m) and the possibility of installation within the foundations of the house. However, it should be noted that the amount of heat that can be obtained depends strongly on the ground type and can differ even 3-4 times in various locations. 5. Heat pumps 173PDF Image | Heat Pumps 978-83-65596-73-4
PDF Search Title:
Heat Pumps 978-83-65596-73-4Original File Name Searched:
Buildings-2020-part2-rozdz5.pdfDIY PDF Search: Google It | Yahoo | Bing
CO2 Organic Rankine Cycle Experimenter Platform The supercritical CO2 phase change system is both a heat pump and organic rankine cycle which can be used for those purposes and as a supercritical extractor for advanced subcritical and supercritical extraction technology. Uses include producing nanoparticles, precious metal CO2 extraction, lithium battery recycling, and other applications... More Info