Text from PDF Page: 027
Chapter No 3 3.1 System performance Evaluation 3.1.1 Coefficient of Performance (COP) Performance of a refrigerating machine (be it a refrigerator or a heat pump) is measured by its coefficient of performance (COP), this COP gives the information about how effectively that machine is utilizing the supplied energy. As in this specific case we are dealing with CO2 heat pump, the objective is to recover maximum heat from the CO2 in the gas cooler by circulating water and mechanical work is supplied as input to compressor to operate the system. The COP is defined as follows, From second law of thermodynamics the COP of any reversible system operating between two temperature limits is exactly same and completely independent of the involved refrigerant, however these are the physical properties of the refrigerants that affect the system power consumption through their influence on the thermodynamic losses. Figure 14 shows one specific case with CO2 where heat was rejected initially at 95 bars from 100 oC (point 2) to 40 oC (point 3) and evaporation temperature was fixed at 0 oC, the COP for the heat pump was 2.7. If the heat could be rejected down to 25 oC while maintaining the same evaporation temperature the COP can be improved up to a value of 3.4. So in order to have a high COP from a CO2 heat pump, the heat has to be rejected over a larger temperature range. 15PDF Image | heat recovery from R744 based refrigeration system
PDF Search Title:
heat recovery from R744 based refrigeration systemOriginal File Name Searched:
r744-heat-recovery.pdfDIY PDF Search: Google It | Yahoo | Bing
CO2 Organic Rankine Cycle Experimenter Platform The supercritical CO2 phase change system is both a heat pump and organic rankine cycle which can be used for those purposes and as a supercritical extractor for advanced subcritical and supercritical extraction technology. Uses include producing nanoparticles, precious metal CO2 extraction, lithium battery recycling, and other applications... More Info
Heat Pumps CO2 ORC Heat Pump System Platform More Info
CONTACT TEL: 608-238-6001 Email: greg@infinityturbine.com | RSS | AMP |