PDF Publication Title:
Text from PDF Page: 005
Application Defined Features & Options COMPRESSORS The MHP chillers feature Scroll compressors with R410A and are available from 15-250 tons. Options for 1,2 or 4 independent refrigerant circuits come with up to 8 compressors, providing unloading for virtually unlimited capacity control. Redundant circuited chillers allow for one circuit to be serviced while the second circuit remains fully operational. Motor over-temperature and current protection provide extended compressor life. CONDENSER FANS The EC TEAO motors feature a reversed stator and rotor, eliminating the traditional motor shaft. The fans are suitable for outdoor use and provide variable speed operation. The industrial design includes composite blades, which do not flex or lose efficiency at the top of their performance curve and allow for reliable low ambient head pressure control. EVAPORATORS The MHP chillers feature either an ASME U and CRN stamped, dual circuited shell & tube evaporator or a brazed plate evaporator. The shell & tube vessel uses a direct expansion design complete with a carbon steel shell and heavy gauge copper tubes while the brazed plate option uses stainless steel plates with copper braze. Both options insure long life cycles and highly efficient heat transfer under varying loads. ADDITIONAL OPTIONS Standard EC fan speed control permits reliable chilled water operation in -20°F (glycol required). Integrated single or double pump options with single point power provide loop circulation within the chiller footprint. Low noise options provide year-round quite operation. Hail guards and condenser filters prevent coil damage and clogging. OUR BUSINESS IS COOLING YOURSTM motivaircorp.comPDF Image | MHP Air Source Heat Pump
PDF Search Title:
MHP Air Source Heat PumpOriginal File Name Searched:
MHP Air Source 2021.pdfDIY PDF Search: Google It | Yahoo | Bing
CO2 Organic Rankine Cycle Experimenter Platform The supercritical CO2 phase change system is both a heat pump and organic rankine cycle which can be used for those purposes and as a supercritical extractor for advanced subcritical and supercritical extraction technology. Uses include producing nanoparticles, precious metal CO2 extraction, lithium battery recycling, and other applications... More Info
Heat Pumps CO2 ORC Heat Pump System Platform More Info
CONTACT TEL: 608-238-6001 Email: greg@infinityturbine.com | RSS | AMP |