Text from PDF Page: 159

Figure 5.30 The measured COP in the DHW mode as a function of the temperature approach at varying DHW temperature. 5 – Experimental Results 4.0 3.5 3.0 2.5 0 5 10 15 20 25 30 Temperature Approach [K] 60°C 70°C 80°C 30 25 20 15 10 5 0 60°C 70°C 80°C 8.0 8.5 9.0 9.5 10.0 10.5 11.0 Gas Cooler Pressure [MPa] Figure 5.31 The measured temperature approach as a function of the high-side pressure at varying DHW temperature. The maximum COPs at 60 and 70oC hot water temperature were measured at approximately 9 and 10 MPa high-side pressure, respectively. At high- side pressures below the optimum values, there was virtually a linear relationship between the COP and the temperature approach as well as between the temperature approach and the high-side pressure. On the other hand, there was only a marginal reduction in the temperature approach when the high-side pressure was increased above the optimum level. By analysing the results in Figure 5.30, it is most likely that the optimum high-side pressure for the 80oC measuring series was above 11 MPa, and that the corresponding temperature approach was around 5 K. 137 Temperature Approach [K] COP [-]

PDF Image | Residential CO2 Heat Pump System for Combined

PDF Search Title:

Residential CO2 Heat Pump System for Combined

Original File Name Searched:

20559406.pdf

DIY PDF Search: Google It | Yahoo | Bing

CO2 Organic Rankine Cycle Experimenter Platform The supercritical CO2 phase change system is both a heat pump and organic rankine cycle which can be used for those purposes and as a supercritical extractor for advanced subcritical and supercritical extraction technology. Uses include producing nanoparticles, precious metal CO2 extraction, lithium battery recycling, and other applications... More Info

Heat Pumps CO2 ORC Heat Pump System Platform More Info

CONTACT TEL: 608-238-6001 Email: greg@infinityturbine.com (Standard Web Page)