Rapport 2414173 - October 2007 __________________________________________________________________ Figure 3 : Comparison of evaporating pressures Note that below a pressure of 5.2 bar, solid and gaseous R744 phases may co-exist at low temperature. This behavior is totally different from that observed with traditional refrigerants, and will have important consequences on the operation, servicing and maintenance of a system working with R744. Figure 3 compares the evaporating operating pressures of R744 to those encountered with R410A and R404A. It can be observed that R744 systems will require to operate a much higher pressures than conventional systems. __________________________________________________________________________________________ SHERPHA PROJECT - Transcritical R744 Heat Pumps – Technician's Manual 11/63PDF Image | Transcritical R744 (CO2) Heat Pumps 2017
PDF Search Title:
Transcritical R744 (CO2) Heat Pumps 2017Original File Name Searched:
Manuel-CO2.pdfDIY PDF Search: Google It | Yahoo | Bing
CO2 Organic Rankine Cycle Experimenter Platform The supercritical CO2 phase change system is both a heat pump and organic rankine cycle which can be used for those purposes and as a supercritical extractor for advanced subcritical and supercritical extraction technology. Uses include producing nanoparticles, precious metal CO2 extraction, lithium battery recycling, and other applications... More Info