19XR,XRV Hermetic Centrifugal Liquid Chillers 50/60 Hz With PIC II Controls and HFC-134a

PDF Publication Title:

19XR,XRV Hermetic Centrifugal Liquid Chillers 50/60 Hz With PIC II Controls and HFC-134a ( 19xrxrv-hermetic-centrifugal-liquid-chillers-50-60-hz-with-p )

Previous Page View | Next Page View | Return to Search List

Text from PDF Page: 037

Table 4 — Capacity Overrides FIRST STAGE SET POINT SECOND STAGE SET POINT View/Modify on CVC Screen Default Value Configurable Range Value SETUP1 125 psig (862 kPa) 90 to 165 psig (620 to 1138 kPa) >Override Set Point +2.4 psid (16.5 kPad) SETUP1 >200 F (93.3 C) 150 to 200 F (66 to 93 C) >Override Set Point +10° F (6° C) SETUP1 3° F (1.6° C) 2° to 5° F (1° to 3° C) ≤Trippoint + Override ∆T –1° F (0.56° C) OPTIONS Min: T1 — 1.5° F (0.8° C) P1 — 50 psid (345 kPad) Max: T2 — 10° F (5.6° C) P2 — 85 psid (586 kPad) 0.5° to 20° F (0.3° to 8.3° C) 30 to 170 psid (207 to 1172 kPad) 0.5° to 20° F (0.3° to 8.3° C) 50 to 170 psid (348 to 1172 kPad) None CAPACITY Automatic 0 to 100% None MAINSTAT 100% 40 to 100% ≥5% of Set Point OVERRIDE Calculated Minimum Superheat for Conditions None 2° F (1.1° C) Below Calculated Minimum Superheat OVERRIDE CAPACITY CONTROL HIGH CONDENSER PRESSURE HIGH MOTOR TEMPERATURE LOW REFRIGERANT TEMPERATURE (Refrigerant Override Delta Temperature) HIGH COMPRESSOR LIFT (Surge Prevention) MANUAL GUIDE VANE TARGET MOTOR LOAD — ACTIVE DEMAND LIMIT LOW DISCHARGE SUPERHEAT Spare Safety Alarm Contacts — One set of alarm contacts is provided in the starter. The contact ratings are pro- vided in the certified drawings. The contacts are located on ter- minal strip JP, terminals 15 and 16. Refrigerant Leak Detector — An input is available on the CCM module [terminal J5-5 (–) and J5-6 (+)] for a refrigerant leak detector. Enabling REFRIGERANT LEAK OPTION (OPTIONS screen) will allow the PIC II controls to go into an alarm state at a user configured level (REFRIGER- ANT LEAK ALARM mA). The input is configured for 4 to 20 mA by setting the DIP switch 1 on SW2 at the ON position, or configured for 1 to 5 vdc by setting switch 1 at the OFF posi- tion. The output of the refrigerant leak detector is displayed as REFRIGERANT LEAK SENSOR on the MAINSTAT screen. For a 1 to 5 vdc input, 1 vdc input represents 4 mA displayed and 5 vdc input represents 20 mA displayed. Kilowatt Output — An output is available on the CCM module [Terminal J8-1 (+) and J8-2 (–)] to represent the power consumption of the chiller. The 4 to 20 mA signal generated by the CCM module can be wired to the building automation or energy management system to monitor the chiller’s energy consumption. A 4 mA signal represents the chiller in an off state and a 20 mA signal represents the chiller operating at its rated peak kilowatt consumption. The rated peak kilowatt con- sumption is configured by the user in the RAM_DEM display screen by the setting the MOTOR RATED KILOWATTS from the job data sheet. Remote Reset of Alarms — A standard feature of the PIC II controls is the ability to reset a chiller in a shutdown alarm state from a remote location. If the condition which caused the alarm has cleared the chiller can be placed back into a normal CCN operating mode when the REMOTE RESET OPTION (CVC_PSWD menu) is set to ENABLE. A variety of Carrier Comfort Network software systems including Comfort- VIEWTM or Network Service ToolTM can access the PIC II controls and reset the displayed alarm. Third party software OVERRIDE TERMINATION Value Trippoint + Override ∆T+2° F (1.2° C) Within Lift Limits Plus Surge/HGBP Deadband Setting Release of Manual Control 2% Lower Than Set Point 1° F (0.56° C) Above Calculated Minimum Superheat from building automation systems (BAS) or energy manage- ment systems (EMS) can also access the PIC II controls through a Carrier DataLINKTM module and reset the fault dis- played. Both methods would access the CVC_PSWD screen and force the RESET ALARM ? point to YES to reset the fault condition. If the PIC II controls have determined that is safe to start the chiller the CCN MODE ? point (CVC_PSWD screen) can be forced to YES to place the chiller back into normal CCN operating mode. The only exceptions are the following alarms that cannot be reset from a remote location: STATE #100, 205, 217-220, 223, 233, 234, 247, and 250. To view alarm codes, refer to Troubleshooting Guide, Checking Dis- play Messages, page 76. After the alarm has been reset the PIC II control will increment the Starts in 12 Hours counter by one upon restart. If the limit of 8 starts in a 12-hour period occurs the alarm will be required to be reset at the chiller control panel (CVC). Condenser Pump Control — The chiller will moni- tor the condenser pressure (CONDENSER PRESSURE) and may turn on the condenser pump if the condenser pressure be- comes too high while the compressor is shut down. The con- denser pressure override (COND PRESS OVERRIDE) parame- ter is used to determine this pressure point. COND PRESS OVERRIDE is found in the SETUP1 display screen, which is accessed from the EQUIPMENT SERVICE table. The default value is 125 psig (862 kPa). If the CONDENSER PRESSURE is greater than or equal to the COND PRESS OVERRIDE, and the entering condenser water temperature (ENTERING CONDENSER WATER) is less than 115 F (46 C), the condenser pump will energize to try to decrease the pressure. The pump will turn off when the con- denser pressure is 3.5 psi (24.1 kPa) less than the pressure over- ride or when the condenser refrigerant temperature (CON- DENSER REFRIG TEMP) is within 3° F (1.7° C) of the enter- ing condenser water temperature (ENTERING CONDENSER WATER). 37

PDF Image | 19XR,XRV Hermetic Centrifugal Liquid Chillers 50/60 Hz With PIC II Controls and HFC-134a

PDF Search Title:

19XR,XRV Hermetic Centrifugal Liquid Chillers 50/60 Hz With PIC II Controls and HFC-134a

Original File Name Searched:

19xr_4ss_Startup_PICII.pdf

DIY PDF Search: Google It | Yahoo | Bing

NFT (Non Fungible Token): Buy our tech, design, development or system NFT and become part of our tech NFT network... More Info

IT XR Project Redstone NFT Available for Sale: NFT for high tech turbine design with one part 3D printed counter-rotating energy turbine. Be part of the future with this NFT. Can be bought and sold but only one design NFT exists. Royalties go to the developer (Infinity) to keep enhancing design and applications... More Info

Infinity Turbine IT XR Project Redstone Design: NFT for sale... NFT for high tech turbine design with one part 3D printed counter-rotating energy turbine. Includes all rights to this turbine design, including license for Fluid Handling Block I and II for the turbine assembly and housing. The NFT includes the blueprints (cad/cam), revenue streams, and all future development of the IT XR Project Redstone... More Info

Infinity Turbine ROT Radial Outflow Turbine 24 Design and Worldwide Rights: NFT for sale... NFT for the ROT 24 energy turbine. Be part of the future with this NFT. This design can be bought and sold but only one design NFT exists. You may manufacture the unit, or get the revenues from its sale from Infinity Turbine. Royalties go to the developer (Infinity) to keep enhancing design and applications... More Info

Infinity Supercritical CO2 10 Liter Extractor Design and Worldwide Rights: The Infinity Supercritical 10L CO2 extractor is for botanical oil extraction, which is rich in terpenes and can produce shelf ready full spectrum oil. With over 5 years of development, this industry leader mature extractor machine has been sold since 2015 and is part of many profitable businesses. The process can also be used for electrowinning, e-waste recycling, and lithium battery recycling, gold mining electronic wastes, precious metals. CO2 can also be used in a reverse fuel cell with nafion to make a gas-to-liquids fuel, such as methanol, ethanol and butanol or ethylene. Supercritical CO2 has also been used for treating nafion to make it more effective catalyst. This NFT is for the purchase of worldwide rights which includes the design. More Info

NFT (Non Fungible Token): Buy our tech, design, development or system NFT and become part of our tech NFT network... More Info

Infinity Turbine Products: Special for this month, any plans are $10,000 for complete Cad/Cam blueprints. License is for one build. Try before you buy a production license. May pay by Bitcoin or other Crypto. Products Page... More Info

CONTACT TEL: 608-238-6001 Email: greg@infinityturbine.com (Standard Web Page)