Industrial Heat Pumps

PDF Publication Title:

Industrial Heat Pumps ( industrial-heat-pumps )

Previous Page View | Next Page View | Return to Search List

Text from PDF Page: 035

Basics of Industrial Heat Pumps 2-35 Physical principles represents the upper theoretical value obtainable in a heat pump system. In practice attainable coefficients of performance are significantly less than COPc. Unfor- tunately, it is difficult to compare the COPs of different categories of IHP, which differ widely for equivalent economic performance. When comparing heat pump systems driven by different energy sources it is more appropriate to use the primary energy ratio (PER) defined as 𝑃𝐸𝑅 = 𝑒𝑠𝑒𝑓𝑒𝑙𝑙 hπ‘’π‘Žπ‘‘ π‘‘π‘’π‘™π‘–π‘£π‘’π‘Ÿπ‘’π‘‘ π‘π‘Ÿπ‘–π‘šπ‘Žπ‘Ÿπ‘¦ π‘’π‘›π‘’π‘Ÿπ‘”π‘¦ 𝑖𝑛𝑝𝑒𝑑 The equation can be related to the coefficient of performance by the equation 𝑃𝐸𝑅= πœ‚Γ—πΆπ‘‚π‘ƒ where ƞ is the efficiency with which the primary energy input is converted into work up to the shaft of the compressor.

PDF Image | Industrial Heat Pumps

PDF Search Title:

Industrial Heat Pumps

Original File Name Searched:

annex-xiii-part-a.pdf

DIY PDF Search: Google It | Yahoo | Bing

CO2 Organic Rankine Cycle Experimenter Platform The supercritical CO2 phase change system is both a heat pump and organic rankine cycle which can be used for those purposes and as a supercritical extractor for advanced subcritical and supercritical extraction technology. Uses include producing nanoparticles, precious metal CO2 extraction, lithium battery recycling, and other applications... More Info